Sign In | Join Free | My infospaceinc.com
China Shenzhen Jianhong Jitai Technology Co., Ltd. logo
Shenzhen Jianhong Jitai Technology Co., Ltd.
Shenzhen Jianhong Jitai Technology Co., Ltd.
Verified Supplier

2 Years

Home > Resistive Load Bank >

22 KW Three - phase 480 V High - power Adjustable Load

Shenzhen Jianhong Jitai Technology Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now

22 KW Three - phase 480 V High - power Adjustable Load

  • 1
  • 2
  • 3

Packaging Details : Wooden box

Loading Port : China

Model Number : JH-RYF-22KWA480-W9K

MOQ : 1

Resistance Accuracy : ±3%

Delivery Time : 20-25 working days

Accuracy Class : 1kw

Payment Terms : T/T

Resistance Accuracy : ±3%(Sheet resistor)

Operatingtemperaturerange : -10°C to 50°C (typical)

Brand Name : Jianhong

Certification : CE

Place of Origin : China

Auxiliary Voltage : AC220V

Contact Now

22 kW, three-phase, 480 V, high-power adjustable load
Core Features of the Product
High-power stable load, high-precision resistor

Rated three-phase output of 480 V at 22 kW high power, featuring chip resistors with ±3% resistance accuracy and a power factor up to 0.99. The system provides synchronized balanced loading across all phases, ensuring stable load performance without phase imbalance.

Powerful air-cooled cooling for long-lasting continuous operation

Equipped with six 15050 AC220V industrial fans, the air ducts deliver forced air cooling from right to left for high heat dissipation efficiency. It supports 24/7 uninterrupted continuous operation and is designed for prolonged aging test conditions.

Multiple security protections for reliable use

It features a four-tier protection system comprising overheat alarm, 1.1 times rated voltage overvoltage protection, overcurrent protection, and emergency shutdown; with an indoor IP20 protection rating that effectively mitigates risks of overload, overheating, and overvoltage faults.

Power supply configuration is clear and wiring is simple

Main load: three-phase 480 V input; auxiliary control power: AC 220 V, 50 Hz. The load is connected via terminal blocks, while the system power supply uses standard sockets for easy wiring.

Applicable Scenarios
Aging Test for Energy Storage Power Sources and Three-Phase Inverters

480V three-phase energy storage converter, photovoltaic inverter, and high-power UPS subjected to full-load aging tests and power stability testing upon factory delivery

Load test of generator sets and three-phase DC power supplies

Performance testing of small-to-medium three-phase diesel/gasoline generators and high-power three-phase voltage-regulated power supplies under full-load conditions regarding power output, voltage drop, and temperature rise.

Acceptance testing of charging piles and high-power power supply equipment

High-power three-phase DC charging station rated at 480 V; comprehensive factory testing simulating full-load operating conditions for industrial power supplies

Type testing of electrical equipment before it leaves the factory

Temperature rise under continuous load and overload protection function verification for distribution cabinets, terminal blocks, and three-phase power supply modules

Frequently Asked Questions

Q1: Can this load cabinet be loaded phase by phase separately?

A: No. The equipment loads all three phases simultaneously and synchronously, with the three-phase loads outputting together; it cannot independently adjust the load for each phase (A, B, or C).

Q2: Can the system continue operating with a faulty fan?

A: The six 220V cooling fans are critical components for forced air cooling. A damaged fan can rapidly cause resistor overheating, triggering an overheating protection shutdown. If a fan failure is detected, immediately shut down the system, replace the fan, and resume operation.

Q3: Can the load power be adjusted in segments?

A: The system uses circuit breakers to adjust power in segments. By opening and closing circuit breakers at different power levels, adjustable load output within the range of 0–22 kW can be achieved.

Q4: Will the system automatically shut down if the ambient temperature is too high?

A: The maximum operating temperature is 50°C, and the device features overheat protection. An overheat alarm will be triggered in cases of blocked cooling ducts, excessive ambient temperature, or fan failure; in severe cases, the system will automatically disconnect the load protection resistor.

Product Parameters
Product Parameter Specifications
model JH-RYF-22KWA480-W9K
brand Jianhong
size ≤400*550*770MM(length * width * height)
weight ≤50KG
power rating 22KW
rated voltage 480 V (three-phase)
accessory power supply AC220V 50HZ
power factor 0.99
Resistance Precision ±3%(Sheet resistor)
Cold Road Forced air cooling, from right to left: 6 15050 fans (operating on 220 V AC power supply).
work environment Working environment temperature: -10°C to 50°C, dry and well-ventilated
Local Control Method air switch
Remote Control Method NO
IP grade IP20 (Indoor)
Load Description Three phases loaded simultaneously
display mode Show power, current, voltage, etc.
Load Protection Overheat alarm, overvoltage protection (circuit breaker activation at 1.1 times rated voltage), overcurrent protection, emergency stop
operate mode Available for continuous online operation 24/7 with a 1-year warranty.
Load Connection Method wiring terminal
System Power Supply Wiring Method convenienve receptacle
Mobile Mode Handheld casters

Quality 22 KW Three - phase 480 V High - power Adjustable Load for sale

22 KW Three - phase 480 V High - power Adjustable Load Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Shenzhen Jianhong Jitai Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)